Voltage and Continuous, Short-Time, and Fault-Closing Ratings
kV | Amperes, RMS | |||||
---|---|---|---|---|---|---|
Nom. | Max | BIL | Cont. | Short-Time | Fault-Closing, Duty-Cycle, One-Time | |
Mom. | 3-Second | |||||
34.5 | 38 | 200 | 1200 | 61 000 | 40 000 | 30 000 |
46 | 48.3 | 250 | 1200 | 61 000 | 40 000 | 30 000 |
69 | 72.5 | 350 | 1200 | 61 000 | 40 000 | 30 000 |
115 | 121 | 550 | 1200 | 61 000 | 40 000 | 30 000 |
138 | 145 | 650 | 1200 | 61 000 | 40 000 | 30 000 |
1600♥ | 70 000 | 43 750 | 40 000 | |||
2000♥ | 80 000 | 50 000 | 40 000 | |||
161 | 169 | 750 | 1200 | 61 000 | 40 000 | 30 000 |
230 | 242 | 900 | 1600 | 70 000 | 43 750 | 40 000 |
2000 | 80 000 | 50 000 | 40 000 | |||
345 | 362 | 1300 | 1600 | 70 000 | 43 750 | 40 000 |
2000 | 80 000 | 50 000 | 40 000 |
♥ 1600 and 2000 amperes continuous available in Three-Pole Center-Break style only.
Interrupting Current Ratings for Transformer Switching and Protection
Mastertrol Mark V Installation Manual Pdf
Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
---|---|---|
Parallel Switching | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000♥ |
Load Dropping and Magnetizing Current Switching | Transformers connected to solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000♥♣ |
All other connections of transformers | 1200/1600/2000♥♣ | |
Fault Interrupting | Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than ♠. | 7000 or 8000 |
Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher less than ♠. | 4000 (3000A for 115-kV single-gap Circuit-Switchers) | |
Secondary faults — all other connections of transformers | 4000 (3000A for 115-kV single-gap Circuit-Switchers) | |
Internal faults — see both primary and secondary faults, above |
Mark V Circuit-Switcher Effective overvoltage control for capacitor-bank switching and transmission line full-load-current switching applications. The S&C Mark V Circuit-Switcher is the perfect solution for growing your grid without spending time and money on a new substation. Installation Instructions Front Terminal Side The Motor Switch Terminal, Model MST, is a 24 Volt, AC two-position motor. Honda Accord Parts Manual here. This motor is used with Trol-A-Temp and EWC. MOTOR TERMINALS ON MASTERTROL MARK IV, V, VII, VIII, X, XXX, AND XXXI. 12 4 5 3 6 X Z M6 M5 M4 M2 M1 CLOSED OPEN 24 VOLTS NOTE: When using a.
♥ Depending on continuous rating of Circuit-Switcher.
♣ Will switch magnetizing currents associated with such loads.
♠ Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
Aqua-Magic® V Hand Flush. Owners Manual - Aqua Magic V (Foot and Hand flush) Service Kit - 01665 - AM5 Curved Hose Adapter; Service Kit - 28962 - Water Line Extension Hose. The MDP3 Control is a two (2) and three (3) zone, expandable (103 zones) control panel can be usedthat with conventional single stage and two stage heating and cooling, heat pumps with.
Mastertrol Mini Zone
System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
---|---|---|---|---|---|
Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
Interrupting Current Ratings for Line Switching and Protection
Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
---|---|---|
Load Splitting (Parallel or Loop Switching) | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000♥ |
Load Dropping | Circuits with all load-side transformers connected solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000♥ |
Circuits with all load-side transformers connected other than as described above. | 1200/1600/2000♥ | |
Line Dropping | Maximum length of line: 300 miles. | |
Fault Interrupting | Line or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than ♠. | 7000 or 8000 |
Line or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher less than ♠. | 4000 (3000A for 115-kV single-gap Circuit-Switchers) |
♥ Depending on continuous rating of Circuit-Switcher.
♠ Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
---|---|---|---|---|---|
Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
Interrupting Current Ratings for Cable Switching and Protection
Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical |
---|---|---|
Load Splitting (Parallel or Loop Switching) | Max 60-hertz recovery voltage: 90 kV RMS and 150 kV RMS | 1200/1600/2000♥ |
Load Dropping | Circuits with all load-side transformers connected solidly grounded-wye on the primary (Circuit-Switcher) side and delta on the secondary side | 1200/1600/2000♥ |
Circuits with all load-side transformers connected other than as described above. | 1200/1600/2000♥ | |
Cable Dropping (Charging Current) | Shielded and Unshielded Cable | 550 |
Fault Interrupting | Cable or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than ♠. | 7000 or 8000 |
Cable or bus faults with the total connected length of all lines on the source side of the Circuit-Switcher less than ♠. | 4000 (3000A for 115-kV single-gap Circuit-Switchers) |
♥ Depending on continuous rating of Circuit-Switcher.
♠ Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
Mastertrol Mark V Manual
System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
---|---|---|---|---|---|
Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
Fl studio 20 custom skins download.
Interrupting Current Ratings for Shunt Capacitor Bank Switching and Protection
Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical | |
---|---|---|---|
Bank Current Switching | Grounded capacitor bank | Applications on solidly grounded systems through 69 kV | 1000 |
All other applications | 550 | ||
Ungrounded capacitor bank | 550 | ||
Fault Interrupting | Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher not less than ♠. | 7000 or 8000 | |
Primary faults with the total connected length of all lines on the source side of the Circuit-Switcher less than ♠. | 4000 (3000A for 115-kV single-gap Circuit-Switchers) |
♠ Total connected length of all ovehead lines (in all directions) including any number of feeders connected to source-side substations as indicated in the table below:
Mastertrol Mark V Installation Manual Transfer Switch
System Voltage, kV | 34.5 thru 69 | 115 and 138 | 161 | 230 | 345 |
---|---|---|---|---|---|
Total Length, Miles | 7 | 15 | 20 | 25 | 40 |
Mastertrol Mark V Installation Manuals
Interrupting Current Ratings for Reactor Switching and Protection
Mastertrol Mark V Installation Manual Transmission
Class | Qualifications | Maximum Amperes, Interrupting RMS Symmetrical | |
---|---|---|---|
Series Reactor Switching | Refer to the nearest S&C Sales Office. | ||
Shunt Reactor Switching and Protection (Line-Connected or Tertiary Connected Reactors) | Reactor Current Switching | Reactor wye-connected with solidly grounded neutral | 1000 |
Reactor delta-connected, or wye-connected with ungrounded neutral | 1000 | ||
Fault Interrupting | Oil-insulated reactors | 2800 | |
Air-insulated reactors | 2000 |